1.3.2 Mode-2
In MODE-2 (switch 1 ON), the monitor relay is typically connected to a local alarm (bell, buzzer, light,
etc.) and the alarm relay is typically connected to the buildings alarm system. In this mode, there are
two distinct conditions under which the tracker board will respond to a door ajar condition; FORCED
CONDITION and PROPER CONDITION.
FORCED CONDITION - The access system or request to exit device has not activated the door strike
(output relay not activated) but the door ajar contact (door ajar switch closes) indicates that the door
has been opened. In a forced condition, both the monitor relay and alarm relay will activate whenever
the door ajar switch is closed, and will deactivate when the door ajar switch opens. Note that a forced
condition can only occur if the access system or request to exit device has not activated the door
strike, otherwise a proper condition occurs.
PROPER CONDITION - The access system or request to exit device has activated the door strike
(output relay activated), but the door has not closed (door ajar switch closed) by the end of the strike
time. In a proper condition, the monitor relay will go on and off at 1-second intervals until the door
closes (door ajar switch opens), or until the door ajar timer (switches 5 & 6) runs out. Five seconds
prior to the door ajar timer running out, the monitor relay will stay on, and then deactivate. When the
door ajar timer runs out, the alarm relay may or may not activate depending on the setting of switches
3 & 4. If the alarm relay does activate (switches 3 & 4 off), it will remain activated until the door closes
(door ajar switch opens).
MODE-2 OPERATION SWITCH SETTINGS
Switch Description Setting Function
1 Mode ON Sets board to operate in MODE-2 condition.
2 Spare OFF Not used in MODE-2 operation. Leave OFF.
3 & 4 Condition
(See combinations
below and chart on
next page)
3
OFF
OFF
ON
ON
4
OFF
ON
OFF
ON
Sets tracker board for the following conditions.
1 - Forced & Proper conditions enabled.
2 - Forced condition only enabled.
3 - Proper condition only enabled.
4 - Forced & Proper conditions enabled.
5 & 6 Door ajar timer 5
ON
OFF
ON
OFF
6
ON
ON
OFF
OFF
How long monitor relay activates after a door ajar condition exist.
30 Seconds
1 Minute
3 Minutes
5 Minutes
7 & 8 Output relay strike
time
7
ON
OFF
ON
OFF
8
ON
ON
OFF
OFF
Output relay strike time after access is granted.
1 Second
3 Seconds
5 Seconds
30 Seconds
In MODE-2, the setting of switches 3 & 4 will determine which conditions (proper, forced) the tracker
board will respond to, and how the monitor and alarm relays will respond under a proper condition
(see chart on next page).
CONDITION COMBINATIONS
1. Forced and Proper condition enabled (Switch 3 OFF - Switch 4 OFF).
Monitor and Alarm
relay respond to a Proper condition.
2. Forced condition only enabled (Switch 3 OFF - Switch 4 ON).
Monitor and Alarm relays
respond.
3. Proper condition only enabled (Switch 3 ON - Switch 4 OFF).
Monitor relay only responds.
4. Forced and Proper condition enabled (Switch 3 ON - Switch 4 ON).
Monitor relay only
responds to a Proper condition.